Three Panel Workstation Fire
Three panel workstation fire time-line
This test was sponsored by the
General Services Administration (GSA)
and performed at
BFRL
in 1991.
Times are in seconds from ignition.
Select a picture to view a larger version.
| 0 min, 30 kW |
1 min, 190 kW |
2 min, 220 kW |
3 min, 260 kW |
4 min, 110 kW |
 |
 |
 |
 |
 |
| 5 min, 150 kW |
6 min, 860 kW |
7 min, 1.0 MW |
8 min, 2.8 MW |
9 min, 6.6 MW |
 |
 |
 |
 |
 |
| 10 min, 3.2 MW |
11 min, 2.1 MW |
12 min, 1.4 MW |
14 min, 630 kW |
16 min, 690 kW |
 |
 |
 |
 |
 |
| 18 min, 480 kW |
22 min, 530 kW |
26 min, 390 kW |
30 min, 370 kW |
34 min, 350 kW |
 |
 |
 |
 |
 |
The fire size in kilowatts versus time
Fire Data
The heat release data for this case is incorporated into
the default one-room case for
CFAST/FASTLite.
If you are running FASTLite,
we suggest that you copy this file into the default
example directory, C:\FLITE .
The data is also available in a
spread sheet (comma delimited) format.
Animations
View a movie of this fire
by downloading one
of the following quicktime or mpeg files.