Two Panel Workstation Fire
Two panel workstation fire time-line
This test was sponsored by the
General Services Administration (GSA)
and performed at
BFRL
in 1991.
Times are in seconds from ignition.
Select a picture to view a larger version.
| 0 min, 0 kW |
1 min, 10 kW |
2 min, 70 kW |
3 min, 215 kW |
4 min, 680 kW |
 |
 |
 |
 |
 |
| 5 min, 1.7 MW |
6 min, 1.4 MW |
7 min, 1.5 MW |
8 min, 1.3 MW |
9 min, 1.3 MW |
 |
 |
 |
 |
 |
| 10 min, 1.1 MW |
12 min, 960 kW |
14 min, 880 kW |
16 min, 690 kW |
18 min, 710 kW |
 |
 |
 |
 |
 |
| 20 min, 750 kW |
22 min, 730 kW |
24 min, 600 kW |
26 min, 530 kW |
28 min, 480 kW |
 |
 |
 |
 |
 |
| 30 min, 490 kW |
34 min, 400 kW |
38 min, 380 kW |
42 min (no data) |
 |
 |
 |
 |
The fire size in kilowatts versus time
Fire Data
The heat release data for this case is incorporated into
the default one-room case for
CFAST/FASTLite.
If you are running FASTLite,
we suggest that you copy this file into the default
example directory, C:\FLITE .
The data is also available in a
spread sheet (comma delimited) format.