Sofa Fire
Sofa fire time-line
Times are in seconds from ignition.
Select a picture to view a larger version.
| 0 s, 0 kW |
30 s, 8 kW |
60 s, 16 kW |
90 s, 83 kW |
 |
 |
 |
 |
| 120 s, 230 kW |
150 s, 450 kW |
180 s, 790 kW |
210 s, 1.1 MW |
 |
 |
 |
 |
| 240 s, 1.5 MW |
270 s, 1.7 MW |
300 s, 1.9 MW |
330 s, 1.9 MW |
 |
 |
 |
 |
| 360 s, 2.6 MW |
390 s, 3.5 MW |
420 s, 3.1 MW |
450 s, 2.3 MW |
 |
 |
 |
 |
| 480 s, 2.0 MW |
510 s, 1.4 MW |
540 s, 950 kW |
 |
 |
 |
The fire size in kilowatts versus time
Fire Data
The heat release data for this case is incorporated into
the default one-room case for
CFAST/FASTLite.
If you are running FASTLite,
we suggest that you copy this file into the default
example directory, C:\FLITE .
The data is available in a generic
spread sheet (comma delimited) format
and in an
Excel worksheet format.
Data for the loveseat and sofa is also available in both
a generic (comma delimited) format and
Excel worksheet format.
Animations
View a movie of this fire
by downloading one
of the following
mpeg (750 k)
or
quick time (1.2 m) files.