Loveseat Fire
Loveseat fire time-line
Times are in seconds from ignition.
Select a picture to view a larger version.
| 0 s, 0 kW |
26 s, 0 kW |
56 s, 28 kW |
86 s, 121 kW |
 |
 |
 |
 |
| 116 s, 295 kW |
146 s, 400 kW |
176 s, 574 kW |
206 s, 750 kW |
 |
 |
 |
 |
| 236 s, 1.1 MW |
266 s, 1.7 MW |
296 s, 2.1 MW |
326 s, 2.6 MW |
 |
 |
 |
 |
| 356 s, 3.0 MW |
386 s, 2.8 MW |
416 s, 2.4 MW |
446 s, 1.5 MW |
 |
 |
 |
 |
The fire size in kilowatts versus time
Fire Data
The heat release data for this case is incorporated into
the default one-room case for
CFAST/FASTLite.
If you are running FASTLite,
we suggest that you copy this file into the default
example directory, C:\FLITE .
The data is available in a generic
spread sheet (comma delimited) format
and in an
Excel worksheet format.
Data for the loveseat and sofa is also available in both
a generic (comma delimited) format and
Excel worksheet format.
Animations
View a movie of this fire
by downloading on of the following: