FASTData January 1999 Release

Test Type: Cone Calorimeter, Test Number: T6043, Description File: t6043



Descriptions
FDMS: Obtaining Data
Documentation
Abstract:
Computer-Aided Molecular Design of Fire Resistant Aircraft Materials.
Material:Polypropylene (Liquid)
Lab:National Institute of Standards and Technology
Sponsor:National Institute of Standards and Technology
Date:9/21/1993
Test Ref No:T6043
Tested by:Jack Lee
Approved by
Scientific Officer:
James Brown

Test Results (summary)

Mass Lost:4895 g/m2 Total Heat Released:200.836 MJ/m2
Peak RHR:1266.67 kW/m2Peak Mass Loss Rate:30.4887 g/m2s

Summary Data From Ignition

Units Test Mean 60 s 180 s 300 s
Heat Release kW/m2 692.7 237.646 521.283 668.504
Mass Loss Rate g/m2s 0.0206501 0.00538991 0.0120588 0.0163167
Heat of CombustionMJ/kg41028700 44.091 43.2285 40.9707
Specific Ext. Aream2/kg - - - -
Carbon Dioxidekg/kg 3.34284 3.96532 3.70488 3.34284
Carbon Monoxidekg/kg 0.0336661 0.0147579 0.0279635 0.0336661

Observations and Comments

Flaming out time 8 minute 30 seconds.




Details of Test Procedure Used

Heat Flux: 20 kW/m2 Nominal Flow:24 l/s
Orifice Constant: 0.0428552 Heat per Unit Mass O2:13.1 J/kg
Heater Orientation:H Spark Ignitor Used:Y
Grid Used: N Frame Used:N
Conditioning: 50 RH @ 296 K Test Conditions: 50 RH
Specimen Thickness:- Specimen Area:0.004418 m2

Test Results

Initial Mass: 0.02169 g Time of Peak RHR: 455 s
Final Mass: 6.39038e-05 g Peak RHR: 1266.67 kW/m2
Mass Lost: 4895 g/m2 Peak Mass Loss Rate: 30.4887 g/m2s
Ignition Time:217 s Peak Extinction Area:-
Flameout Time:512 s Total Heat Released: 200.836 MJ/m2

Test Quality Indicators

Publication Status:Unpublished
Statistical Basis of Data:Replicate data available for the same test method and test conditions
Material Development/
Production Status:
Experimental material
Evaluation Status:Data have been validated
Laboratory
Accreditation Status:
The laboratory is recognized by (inter)national accreditation bodies
Completeness of
Material Description:
Partial information on material
Completeness of Test
Procedure Description:
Standard test procedure

Test Results (summary)

Data Plots

Heat release rate per unit area

Mass Loss Rate Per Unit Area

CO2 Yield

CO Yield

Soot Flow Rate

Smoke Extinction Area


FASTData Home
Building and Fire Research Laboratory
National Institute of Standards and Technology
Gaithersburg, MD 20899