FASTData January 1999 Release

Test Type: Cone Calorimeter, Test Number: T5794, Description File: t5794



Descriptions
FDMS: Obtaining Data
Documentation
Abstract:
NIST / Dupont CRADA.
Material:Polyethylene 60%, Polypropylene 40%
Lab:National Institute of Standards and Technology
Sponsor:National Institute of Standards and Technology
Date:2/8/1993
Test Ref No:T5794
Tested by:Jack Lee
Approved by
Scientific Officer:
James Brown

Test Results (summary)

Mass Lost:6888.54 g/m2 Total Heat Released:266.268 MJ/m2
Peak RHR:238.722 kW/m2Peak Mass Loss Rate:5.52786 g/m2s

Summary Data From Ignition

Units Test Mean 60 s 180 s 300 s
Heat Release kW/m2 170.694 104.17 146.553 158.721
Mass Loss Rate g/m2s 0.00460055 0.00243628 0.00358755 0.00389229
Heat of CombustionMJ/kg37835600 39.9579 40.2188 40.3844
Specific Ext. Aream2/kg - - - -
Carbon Dioxidekg/kg 2.99379 2.20783 2.90902 3.05447
Carbon Monoxidekg/kg 0.0168367 0.00477996 0.010319 0.0131606

Observations and Comments

Flaming out time 40 min. 29 sec.. Sample smokes 3 min.50sec.
and Top surface charring 7 minutes. Flames top surface and
layers of polymer below 14 min. 45 sec.. Sample turn into
charring boil liquid 25 minutes. Sample is 40mm below cone
at start.TUH is down-NO SOOT-Ascarite and drierite used

Details of Test Procedure Used

Heat Flux: 20 kW/m2 Nominal Flow:24 l/s
Orifice Constant: 0.0432687 Heat per Unit Mass O2:12.98 J/kg
Heater Orientation:H Spark Ignitor Used:Y
Grid Used: N Frame Used:N
Conditioning: 50 RH @ 296 K Test Conditions: 50 RH
Specimen Thickness:- Specimen Area:0.00442 m2

Test Results

Initial Mass: 0.0296 g Time of Peak RHR: 1915 s
Final Mass: - Peak RHR: 238.722 kW/m2
Mass Lost: 6888.54 g/m2 Peak Mass Loss Rate: 5.52786 g/m2s
Ignition Time:862 s Peak Extinction Area:-
Flameout Time:2428 s Total Heat Released: 266.268 MJ/m2

Test Quality Indicators

Publication Status:Unpublished
Statistical Basis of Data:Single point value
Material Development/
Production Status:
Experimental material
Evaluation Status:Data have been validated
Laboratory
Accreditation Status:
The laboratory is recognized by (inter)national accreditation bodies
Completeness of
Material Description:
Partial information on material
Completeness of Test
Procedure Description:
Standard test procedure

Test Results (summary)

Data Plots

Heat release rate per unit area

Mass Loss Rate Per Unit Area

CO2 Yield

CO Yield

Smoke Extinction Area


FASTData Home
Building and Fire Research Laboratory
National Institute of Standards and Technology
Gaithersburg, MD 20899